As Ayaka reported the thermal was abormal on rk3288 at booting time.
thermal thermal_zone1: critical temperature reached(125 C),shutting down
thermal thermal_zone2: critical temperature reached(125 C),shutting down
thermal thermal_zone1: critical temperature reached(125 C),shutting down
thermal thermal_zone2: critical temperature reached(125 C),shutting down
...
The root caused by reading the invald analogic value, the value is zero
will convert the 125 degree to trigger the critical temperature.
Fixes it with insteading of the incorrect reading now.
Fixes commit cadf29dc2a8bcaae83
("thermal: rockchip: optimize the conversion table")
Reported-by: ayaka <ayaka@soulik.info>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
| |
In some cases, some sensors didn't need the trip points, the
set_trips will pass {-INT_MAX, INT_MAX} to trigger tsadc alarm in the end,
ignore this case and disable the high temperature interrupt.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Reviewed-by: Brian Norris <briannorris@chromium.org>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
In order to support the valid temperature can conver to analog value.
The rockchip thermal driver has not supported the all valid temperature
to convert the analog value. (e.g.: 61C, 62C, 63C....)
For example:
In some cases, we need adjust the trip point.
$cd /sys/class/thermal/thermal_zone*
$echo 68000 > trip_point_0_temp
That will return the max analogic value indicates the invalid before
posting this patch.
So, this patch will optimize the conversion table to support the other
cases.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
| |
The temp_to_code function will return 0 when we set the temperature to a
invalid value (e.g. 61C, 62C, 63C....), that's unpractical. This patch
will prevent this case happening. That will return the max analog value to
indicate the temperature is invalid or over table temperature range.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
| |
This driver passes struct chip_tsadc_table by value throughout; this is
inefficient, and AFAICT, there is no reason for it. Let's pass pointers
instead.
Signed-off-by: Brian Norris <briannorris@chromium.org>
Reviewed-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
These error messages don't give much information about what went wrong.
It would be nice, for one, to see what invalid temperature was being
requested when conversion fails. It's also good to return an error when
we can't handle a conversion properly.
While we're at it, fix the grammar too.
Signed-off-by: Brian Norris <briannorris@chromium.org>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
It is no necessary to print warning agian and again if we don't
add rockchip,grf for dt, otherwise I saw the following log when
doing suspend-2-resume. We only need to print it once when parsing
dt. It looks quite trivial but the log is apparently verbose.
[ 26.615415] PM: early resume of devices complete after 1.539 msecs
[ 26.622002] rk_tsadcv2_initialize: Missing rockchip,grf property
[ 26.629359] rk_gmac-dwmac ff290000.ethernet: init for RGMII
[ 26.639794] PM: resume of devices complete after 18.109 msecs
[ 26.646925] Restarting tasks ... done.
Reviewed-by: Caesar Wang <wxt@rock-chips.com>
Reviewed-by: Heiko Stuebner <heiko@sntech.de>
Signed-off-by: Shawn Lin <shawn.lin@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Added one additional parameter to thermal_zone_device_update() to provide
caller with an optional capability to specify reason.
Currently this event is used by user space governor to trigger different
processing based on event code. Also it saves an additional call to read
temperature when the event is received.
The following events are cuurently defined:
- Unspecified event
- New temperature sample
- Trip point violated
- Trip point changed
- thermal device up and down
- thermal device power capability changed
Signed-off-by: Srinivas Pandruvada <srinivas.pandruvada@linux.intel.com>
Signed-off-by: Zhang Rui <rui.zhang@intel.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
In less than 10 ms, the temperature of soc will arise 10 degree. 250 ms
is too big for soc tempeture control. Setting 2.5 ms will speed up
temperature accessing speed but introduce no more cpu's computing overhead.
We set AUTO_PERIOD_TIME and TSADCV3_AUTO_PERIOD_HT_TIME the same value,
because normal temperature update speed is also our consern in IPA.
Signed-off-by: Rocky Hao <rocky.hao@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Cc: linux-pm@vger.kernel.org
Tested-by: Stephen Barber <smbarber@chromium.org>
Signed-off-by: Zhang Rui <rui.zhang@intel.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Due to the voltage ripple, the sensing data of the tsadc is not accurate.
And in this patch, the bandgap feature is enhanced to remove the voltage
ripple, and then the tsadc can sense the temperature more precisely.
Obsolete codes are removed as well.
Signed-off-by: Rocky Hao <rocky.hao@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Cc: linux-pm@vger.kernel.org
Tested-by: Stephen Barber <smbarber@chromium.org>
Signed-off-by: Zhang Rui <rui.zhang@intel.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
The hardware-tracked trips will set the alarm interrupt value for
registers. Then when the thermal zone has no trips to be set,
That make the thermal trips callback a over range value.
The root cause is the rk_tsadcv2_temp_to_code() function to handle the
invalid temperature range is indeed incorrect, let's fix it on now.
Otherwise, the thermal alarm interrupt will be triggered all the time
on some SoCs.
Fox example:
localhost tmp # grep thermal /proc/interrupts; sleep 5;
grep thermal /proc/interrupts
23: 994830 .. GICv3 129 Level rockchip_thermal
23: 1003423 .. GICv3 129 Level rockchip_thermal
Reported-by: Rocky Hao <rocky.hao@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Cc: linux-pm@vger.kernel.org
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
Signed-off-by: Zhang Rui <rui.zhang@intel.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
We should increase the period cycles to save power since the rk3399 has
the high frequency for tsadc clock.
Fixes commit b0d70338bca22cb14
("thermal: rockchip: Support the RK3399 SoCs in thermal driver")
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Cc: linux-pm@vger.kernel.org
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
Signed-off-by: Zhang Rui <rui.zhang@intel.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Whenever the current temperature is updated, the trip points immediately
below and above the current temperature are found. A sensor driver
callback `set_trips' is then called with the temperatures.
Lastly, The sensor will trigger the hardware high temperature interrupts
to increase the sampleing rate and throttle frequency to limit the
temperature rising When performing passive cooling.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: linux-pm@vger.kernel.org
Tested-by: Stephen Barber <smbarber@chromium.org>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
Signed-off-by: Zhang Rui <rui.zhang@intel.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Documentation/timers/timers-howto.txt recommends to use
usleep_range on delays > 10usec.
The usleep_range indeed reduces CPU load, since the udelay will busy wait
for enough loop cycles to achieve the desired delay.
Fixes commit b06c52db39fd ("thermal: rockchip:
handle the power sequence for tsadc controller").
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Suggested-by: Eduardo Valentin <edubezval@gmail.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
| |
To update the notes for keeping in mind that quickly in case
someone re-read this driver in the future.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
| |
The RK3366 SoCs have two Temperature Sensors, channel 0 is for CPU
channel 1 is for GPU.
Signed-off-by: Elaine Zhang <zhangqing@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
This adds the grf property to handle the tsadc power sequence on
rockchip some SoCs.
Verified on rk3399 can work with this patch on now.
while true; do grep "" /sys/class/thermal/thermal_zone[0-1]/temp
sleep .5; done
/sys/class/thermal/thermal_zone0/temp:40555
/sys/class/thermal/thermal_zone1/temp:41111
/sys/class/thermal/thermal_zone0/temp:40555
/sys/class/thermal/thermal_zone1/temp:41111
/sys/class/thermal/thermal_zone0/temp:40555
/sys/class/thermal/thermal_zone1/temp:41666
/sys/class/thermal/thermal_zone0/temp:40555
/sys/class/thermal/thermal_zone1/temp:41111
/sys/class/thermal/thermal_zone0/temp:40555
/sys/class/thermal/thermal_zone1/temp:41111
/sys/class/thermal/thermal_zone0/temp:40555
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
This patch fixes the incorrect conversion table.
The Code to Temperature mapping is updated based on sillcon results.
Fixes commit b0d70338bca22cb14
("thermal: rockchip: Support the RK3399 SoCs in thermal driver").
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
We should judge the table.id[mid].code insearch algorithm on matter the
adc value increment or decrement.
Or otherwise, the temperature return the incorrect value in some cases.
[ 1.438589] adc_val=402,temp=-40000
[ 1.438903] adc_val=403,temp=-39375
[ 1.439217] adc_val=404,temp=-38750
...
[ 1.441102] adc_val=410,temp=-40000
[ 1.441416] adc_val=411,temp=-34445
[ 1.441737] adc_val=412,temp=-33889
...
Let's fix it right now.
Fixes commit 020ba95dbbbe ("thermal: rockchip:
Add the sort mode for adc value increment or decrement").
Reported-by: Rocky Hao <rocky.hao@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
| |
Disable thermal->clk when enabling pclk fails in
resume routine.
Signed-off-by: Shawn Lin <shawn.lin@rock-chips.com>
Reviewed-by: Heiko Stuebner <heiko@sntech.de>
Reviewed-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
This changes the driver to use the devm_ version
of thermal_zone_of_sensor_register and cleans
up the local points and unregister calls.
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Heiko Stuebner <heiko@sntech.de>
Cc: linux-pm@vger.kernel.org
Cc: linux-arm-kernel@lists.infradead.org
Cc: linux-rockchip@lists.infradead.org
Cc: linux-kernel@vger.kernel.org
Tested-by: Caesar Wang <wxt@rock-chips.com>
Reviewed-by: Caesar Wang <wxt@rock-chips.com>
Reviewed-by: Heiko Stuebner <heiko@sntech.de>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
As the TRM says, add the tsadc_q_sel to control the temperature-code
sequence since the rk3228/rk3399 need set this bit (1024 - tsadc_q)
as output.
Fixes: commit
b0d7033 "thermal: rockchip: Support the RK3399 SoCs in thermal driver"
7b02a5e "thermal: rockchip: Support the RK3228 SoCs in thermal driver"
Reported-by: Elaine Zhang <zhangqing@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
| |
This patch renames to be more adapter compatibles since more and more
SoCs are supported in thermal driver.
Reported-by: Huang,Tao <huangtao@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
| |
the calculation use a global table, not their own table.
so adapt the table to the correct one.
Signed-off-by: Elaine Zhang <zhangqing@rock-chips.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
As the Dan report the smatch check the thermal driver warning:
drivers/thermal/rockchip_thermal.c:551 rockchip_configure_from_dt()
warn: impossible condition '(thermal->tshut_temp > ((~0 >> 1))) =>
(s32min-s32max > s32max)'
Although The shut_temp read from DT is u32,the temperature is currently
represented as int not long in the thermal driver.
Let's change to make shut_temp instead of the thermal->tshut_temp for
the condition.
Fixes: commit 437df2172e8d
("thermal: rockchip: consistently use int for temperatures")
Reported-by: Dan Carpenter <dan.carpenter@oracle.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
| |
The RK3399 SoCs have two Temperature Sensors, channel 0 is for CPU.
channel 1 is for GPU.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
| |
The RK3228 SoCs has one Temperature Sensor, channel 0 is for CPU.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
| |
This patchset trys to dictate unified format for driver.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
| |
The RK3368 SoCs support to 2 channel TS-ADC, the temperature criteria
of each channel can be configurable.
The system has two Temperature Sensors, channel 0 is for CPU,
and channel 1 is for GPU.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
| |
As Temperature is currently represented as int not long in the thermal
framework since use int intead of unsigned long/long to represent
temperature to avoid bogus overheat detection when negative temperature
reported.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
| |
The conversion table has the adc value and temperature.
In fact, the adc value only has the increment or decrement mode in
conversion table.
Moment, we can add the sort mode to be better support the *code_to_temp*
for differenr SoCs.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
| |
We should make the conversion table in as a parameter since the different
SoCs have the different conversionion table.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
| |
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
| |
The current driver is default to register the two thermal sensors
in probe since some SoCs maybe only have one sensor for thermal.
In some cases, the channel 0 is not always the cpu or gpu sensor.
So add the channel can be configured for sensors.
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
Missing a include file caused compile error.
drivers/thermal/rockchip_thermal.c: In function 'rockchip_thermal_suspend':
drivers/thermal/rockchip_thermal.c:720:2: error: implicit declaration of function 'pinctrl_pm_select_sleep_state' [-Werror=implicit-function-declaration]
...
Fixes: 7e38a5b1daa1 ("thermal: rockchip: support the sleep pinctrl state
to avoid glitches")
Reported-by: Stephen Rothwell <sfr@canb.auug.org.au>
Reported-by: kbuild test robot <lkp@intel.com>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
Signed-off-by: Linus Torvalds <torvalds@linux-foundation.org>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
When we come out of system suspend state (S3) the tsadc will have been
reset and back at its default state. While reprogramming the tsadc
it's possible that we'll glitch the output and unintentionally cause
the "over temperature" GPIO to be asserted. Since the over
temperature GPIO is often hooked up to something that will cause a
reboot or shutdown in hardware, this glitch can be catastrophic on
some boards.
We'll add support for selecting the "sleep" pinctrl state at suspend
time. Boards can use this to effectively disable the tsadc at suspend
time and avoid glitches when the system is resumed.
Reviewed-by: Douglas Anderson <dianders@chromium.org>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
When requested thermal shutdown signal polarity is low we need to make
sure that the bit representing high level of signal is reset, and not
set all other bits in that register.
Also rename TSADCV2_INT_PD_CLEAR to TSADCV2_INT_PD_CLEAR_MASK to better
reflect its nature.
Acked-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Dmitry Torokhov <dtor@chromium.org>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
We attempted to signal invalid code by returning -EAGAIN from
rk_tsadcv2_code_to_temp(), unfortunately the return value was stuffed
directly into the temperature pointer, potentially confusing upper
layers with temperature of -EINVAL.
Let's split temperature from error/success indicator to avoid such
confusion.
Also change the way we scan the temperature table to start with the 2nd
element so that we do not need to worry that we may reference out of
bounds element while doing binary search and keep checking that we end
up with 'mid' equal to 0 (since we are looking for the temperature that
would fall into interval between the 'mid' and 'mid - 1') .
Tested-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Dmitry Torokhov <dtor@chromium.org>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
The thermal code uses int, long and unsigned long for temperatures
in different places.
Using an unsigned type limits the thermal framework to positive
temperatures without need. Also several drivers currently will report
temperatures near UINT_MAX for temperatures below 0°C. This will probably
immediately shut the machine down due to overtemperature if started below
0°C.
'long' is 64bit on several architectures. This is not needed since INT_MAX °mC
is above the melting point of all known materials.
Consistently use a plain 'int' for temperatures throughout the thermal code and
the drivers. This only changes the places in the drivers where the temperature
is passed around as pointer, when drivers internally use another type this is
not changed.
Signed-off-by: Sascha Hauer <s.hauer@pengutronix.de>
Acked-by: Geert Uytterhoeven <geert+renesas@glider.be>
Reviewed-by: Jean Delvare <jdelvare@suse.de>
Reviewed-by: Lukasz Majewski <l.majewski@samsung.com>
Reviewed-by: Darren Hart <dvhart@linux.intel.com>
Reviewed-by: Heiko Stuebner <heiko@sntech.de>
Reviewed-by: Peter Feuerer <peter@piie.net>
Cc: Punit Agrawal <punit.agrawal@arm.com>
Cc: Zhang Rui <rui.zhang@intel.com>
Cc: Eduardo Valentin <edubezval@gmail.com>
Cc: linux-pm@vger.kernel.org
Cc: linux-kernel@vger.kernel.org
Cc: Jean Delvare <jdelvare@suse.de>
Cc: Peter Feuerer <peter@piie.net>
Cc: Heiko Stuebner <heiko@sntech.de>
Cc: Lukasz Majewski <l.majewski@samsung.com>
Cc: Stephen Warren <swarren@wwwdotorg.org>
Cc: Thierry Reding <thierry.reding@gmail.com>
Cc: linux-acpi@vger.kernel.org
Cc: platform-driver-x86@vger.kernel.org
Cc: linux-arm-kernel@lists.infradead.org
Cc: linux-omap@vger.kernel.org
Cc: linux-samsung-soc@vger.kernel.org
Cc: Guenter Roeck <linux@roeck-us.net>
Cc: Rafael J. Wysocki <rjw@rjwysocki.net>
Cc: Maxime Ripard <maxime.ripard@free-electrons.com>
Cc: Darren Hart <dvhart@infradead.org>
Cc: lm-sensors@lm-sensors.org
Signed-off-by: Zhang Rui <rui.zhang@intel.com>
|
|
|
|
|
|
|
|
|
|
|
|
| |
There is a copy and paste bug, "->clk" vs "->pclk", so we return the
wrong error code here.
Fixes: cbac8f639437 ('thermal: rockchip: add driver for thermal')
Signed-off-by: Dan Carpenter <dan.carpenter@oracle.com>
Reviewed-by: Caesar Wang <wxt@rock-chips.com>
Reviewed-by: Doug Anderson <dianders@chromium.org>
Tested-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Zhang Rui <rui.zhang@intel.com>
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
| |
In general, the kernel should report temperature readings exactly as
reported by the hardware. The cpu / gpu thermal driver works in 5 degree
increments,but we ought to do more accurate. The temperature will do
linear interpolation between the entries in the table.
Test= $md5sum /dev/zero &
$while true; do grep "" /sys/class/thermal/thermal_zone[1-2]/temp;
sleep .5; done
e.g. We can get the result as follows:
/sys/class/thermal/thermal_zone1/temp:39994
/sys/class/thermal/thermal_zone2/temp:39086
/sys/class/thermal/thermal_zone1/temp:39994
/sys/class/thermal/thermal_zone2/temp:39540
/sys/class/thermal/thermal_zone1/temp:39540
/sys/class/thermal/thermal_zone2/temp:39540
/sys/class/thermal/thermal_zone1/temp:39540
/sys/class/thermal/thermal_zone2/temp:39994
Reviewed-by: Dmitry Torokhov <dmitry.torokhov@gmail.com>
Reviewed-by: Daniel Kurtz <djkurtz@chromium.org>
Signed-off-by: Caesar Wang <wxt@rock-chips.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|
|
|
|
|
|
|
| |
This platform_driver does not need to set an owner, it will be populated by the
driver core.
Signed-off-by: Wolfram Sang <wsa@the-dreams.de>
|
|
Thermal is TS-ADC Controller module supports
user-defined mode and automatic mode.
User-defined mode refers,TSADC all the control signals entirely by
software writing to register for direct control.
Automaic mode refers to the module automatically poll TSADC output,
and the results were checked.If you find that the temperature High
in a period of time,an interrupt is generated to the processor
down-measures taken;If the temperature over a period of time High,
the resulting TSHUT gave CRU module,let it reset the entire chip,
or via GPIO give PMIC.
Signed-off-by: zhaoyifeng <zyf@rock-chips.com>
Signed-off-by: Caesar Wang <caesar.wang@rock-chips.com>
Reviewed-by: Dmitry Torokhov <dmitry.torokhov@gmail.com>
Signed-off-by: Eduardo Valentin <edubezval@gmail.com>
|